MTekpro Technologies Private limited ::
B - 229, Greater Kailash N D-110048

+91 9810703882

Mon - Sat 8:30 AM - 7:00 PM

GENERATOR TESTING

CONDITION MONITORING & DIAGNOSTIC TESTING

1.Generators.

GENERATORS (> 5 MW)
RECOMMENDED TEST AS PER IEC

1.Tests on Stator

  • Insulation Resistance and Polarization Index Measurement at recommended test voltage.
  • Capacitance and Tan delta Measurement at 10 kV or Uo Voltage whichever is less.
  • Partial Discharge Measurement at 10 kV or Uo Voltage whichever is less.
  • DC / AC Leakage current Measurement (Hi-Pot test).
  • DC Winding Resistance Measurement at 1A /10A DC constant source.
  • Electro Magnetic Core Imperfection Detection (ELCID) test.

 

2.Tests on Rotor

  • Insulation Resistance and Polarization Index Measurement at recommended test voltage.
  • DC Winding Resistance Measurement at 1A /10A DC constant source.
  • AC Winding Impedance Measurement.
  • RSO Test (Recurrent Surge Oscillograph test).


3. Tests on Exciter Stator and Rotor

  • Insulation Resistance and Polarization Index Measurement at recommended test voltage.
  • DC Winding Resistance Measurement at 1A /10A DC constant source.
  • AC Winding Impedance Measurement.
  • Checking of diodes and fuses.


4. Tests on PMG

  • Insulation Resistance and Polarization Index Measurement at recommended test voltage.
  • DC Winding Resistance Measurement at 1A /10A DC constant source.
  • AC Winding Impedance Measurement

 